Help you to add on 10kV and below substation shunt capacitor device arranged 5 general provisions:
1, indoor high-voltage capacitor device should be providedin a separate room, when the capacitor capacity is small,can be arranged indoors in the high-voltage power distribution, but the device with high voltage distributiondistance shall not be less than 1.5m.
Low voltage capacitor device can be arranged indoors in the low voltage distribution, when the total capacity capacitor is large, it should be set in a separate room.
2, installed in the interior of the assembly type high voltage capacitor group, the lower capacitor bottom from the groundshould not be less than 0.2m, the capacitor bottom from theground not more than 2.5m, the capacitor device to the top of the roof spacing should not be less than 1.0m. high voltage capacitor arrangement should not be more than three layers.
3, the capacitor shell (wide) net distance, a distance not less than 0.1m. capacitor discharge, should not be less than 0.2m.
4, the assembled capacitor group of single row layout, gateand wall distance should be not less than 1.3m; when thedouble row layout, network between the distance of not less than 1.5m.
5 sets of single row layout, capacitor cabinets, cabinet front and wall distance should be not less than 1.5m; when the distance between the double row layout, the counter should be not less than 2.0m.